Project Description
Fuel Moisture Content | 35% – 40% |
Fuel Input per hour | 460 kg/hr |
Thermal Input | 1,205 kWth |
Thermal Output | 1,200 kWth |
Electrical Output | n/a |
Thermal Efficiency – ηNETT | 83.90% |
Energy Centre Footprint | 36m x 66m |
Approx. Flock Size per 6-8 week growing cycle | 340,000 Birds |
DescriptionEmissionEU Limit
Particulate | 2.7mg/m³ | 10.0 mg/m³ |
NOX | 167 mg/m³ | 200 mg/m³ |
SO2 | 18.4 mg/m³ | 50 mg/m³ |
CO | 5.3 mg/m³ | 50 mg/m³ |
Hydrogen Chloride | 2.8 mg/m³ | 10 mg/m³ |